Data Sheet for Product
OPC Object Specifications_2
Siemens
Smart Infrastructure
ID Object Model Description
FS20EN-0350
FS20EN Zone
OPC Item PresentValue
OPC Item Mode Result State
0-Disable
1-Enable
9-Fast
8-Slow
2-Test
285-Walktest
14-Normal
281-Alarm Evaluation Off
0-Quiet 1-Normal Normal
X X X X X X
267-Non Default Mode 0-Disabled Disabled
X X X X X X
267-Non Default Mode 9-Fast Fast
X X X X X X
267-Non Default Mode 8-Slow Slow
X X X X X X
267-Non Default Mode 2-Test Test
X X X X X X
267-Non Default Mode 285-Walktest Walktest
X X X X X X
267-Non Default Mode 281-Off Alarm Evaluation Off Alarm Evaluation
X X X X X X
16-Abnormal 260-Off Temporary Off Temporary
X X X X X X X
1-Pre Alarm 1-Normal Pre Alarm
X X X X
2-Alarm 1-Normal Alarm
X X X X
6-Not Ready 1-Normal Not Ready
X X X X X X
16-Abnormal 1-Normal Abnormal
X X X X X X
The Zone handles the raw alarm information coming from one or more detectors. Different zones
(Automatic, Technical, Gas, Multi, Extinguishing, etc.) can be used depending on purpose.
States
Commands on OPC Item Mode