Data Sheet for Product
OPC Object Specifications
Siemens
Smart Infrastructure
ID Object Model
Description
XNET-0060
XNET Conventional Zone
Device
OPC Item PresentValue
OPC Item Mode Result State 4 - Enable 5 - Disable \ \
0-Quiet 1-Normal Normal X X
2-Alarm 1-Normal Alarm X X
3-Fault 1-Normal Fault X X
267-Non Default Mode 12-Disabled Disabled X X
Result State 4 - Enable 5 - Disable \ \
Normal X X
Alarm X X
Fault X X
Disabled X X
Enabled X X
268-Trouble Bypass
States
OPC Item Conventional.PresentValue
512-Quiet
514-Alarm
515-Fault
267-Non Default Mode
Device capable of supporting Siemens compatible conventional smoke detectors.
States
Commands on OPC Item Mode
Commands on OPC Item Conventional.Present Value