Data Sheet for Product

OPC Object Specifications
Siemens
Smart Infrastructure
ID Object Model
Description
XNET-0140
XNET HCP Output Device
OPC Item PresentValue
OPC Item Mode Result State 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate
0-Quiet 1-Normal Normal X X X X
2-Alarm 1-Normal Alarm X X X X
3-Fault 1-Normal Fault X X X X
267-Non Default Mode 12-Disabled Disabled X X X
Result State 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate
Normal X X X X
Alarm X X X X
Fault X X X X
Disabled X X X X
Enabled X X X X
267-Non Default Mode
268-Trouble Bypass
States
OPC Item Relay1.PresentValue
512-Quiet
514-Alarm
515-Fault
Intelligent control point, capable of switching on and supporting a notification appliance
circuit, telephone, or speaker zone that is remotely located near a detector loop.
States
Commands on OPC Item Mode
Commands on OPC Item Relay1.Present Value