OPC Interface Specifications Version 3.0 XLS Document No.
Siemens Building Technologies XLS Fire Panel This workbook describes the objects provided by the Siemens OPC Data Access Server to represent the XLS fire control unit Legend ID Object Model Description
Siemens OPC Object Specifications ID Object Model Description XLS-0010 XLS Audio Zone Submodule Modules providing amplifier circuits. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled 4 - Enable OPC DA Specifications_V3.0_XLS.
Siemens OPC Object Specifications ID Object Model Description XLS-0020 XLS Ckt Device Output circuit driven by system behavior. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled 4 - Enable OPC DA Specifications_V3.0_XLS.
Siemens OPC Object Specifications ID Object Model Description XLS-0030 XLS Control Submodule Module to send live pages to specific speaker. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled 4 - Enable OPC DA Specifications_V3.0_XLS.
Siemens OPC Object Specifications ID Object Model Description XLS-0040 XLS Conventional Submodule Module that allows conventional smoke detectors to be used with the FireFinder XLS system. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal X 3-Fault 1-Normal Fault X 267-Non Default Mode 12-Disabled Disabled 4 - Enable OPC DA Specifications_V3.0_XLS.xlsx 5 - Disable \ \ X Page 6 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0050 XLS Conventional Zone Device Device capable of supporting Siemens compatible conventional smoke detectors. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal X 2-Alarm 1-Normal Alarm X 3-Fault 1-Normal Fault X 267-Non Default Mode 12-Disabled Disabled 4 - Enable 5 - Disable \ \ X States Commands on OPC Item Conventional.
Siemens OPC Object Specifications ID Object Model Description XLS-0060 XLS DAC Module Digita audio card to control voice-system modules. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 8 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0070 XLS DLC Device loop card. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 9 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0080 XLS Default Device Input/output devices used for speaker, telephone line, municipal tie, leased line, and so on. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal X 2-Alarm 1-Normal Alarm X 3-Fault 1-Normal Fault X 267-Non Default Mode 12-Disabled Disabled 4 - Enable 5 - Disable \ \ X States Commands on OPC Item LED.
Siemens OPC Object Specifications ID Object Model Building Technologies Description States XLS-0080 cont. Commands on OPC Item Switch1.Present Value OPC Item Switch1.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable \ \ X X X States Commands on OPC Item Relay1.Present Value OPC Item Relay1.
Siemens OPC Object Specifications ID Object Model Description XLS-090 XLS Default Module Input/output control modules used for strobe, horn and notification appliance. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled 4 - Enable 5 - Disable \ \ X X OPC DA Specifications_V3.0_XLS.
Siemens OPC Object Specifications ID Object Model Description XLS-0100 XLS Default Submodule Submodules for input/output supervision, especially for voice and audio applications. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled 4 - Enable 5 - Disable \ \ X X OPC DA Specifications_V3.0_XLS.
Siemens OPC Object Specifications ID Object Model Description XLS-0110 XLS Detector Device Smoke and fire detectors. Building Technologies Part I States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal X 2-Alarm 1-Normal Alarm X 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled 4 - Enable \ \ X X States Commands on OPC Item AudBaseAlert.Present Value OPC Item AudBaseAlert.
Siemens OPC Object Specifications ID Object Model Building Technologies Description States XLS-0110 Commands on OPC Item AudBaseEvac.Present Value Part I cont. OPC Item AudBaseEvac.PresentValue Result State 512-Quiet 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X 514-Alarm Alarm X X X 515-Fault Fault X X X 267-Non Default Mode Disabled X X 268-Trouble Bypass Enabled X X X X States Commands on OPC Item AudBaseOther.Present Value OPC Item AudBaseOther.
Siemens OPC Object Specifications ID Object Model Description XLS-0110 XLS Detector Device Smoke and fire detectors. Building Technologies Part II States Commands on OPC Item Ambient.Present Value OPC Item Ambient.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable \ \ X X X States Commands on OPC Item CO.Present Value OPC Item CO.
Siemens OPC Object Specifications ID Object Model Building Technologies Description States XLS-0110 Commands on OPC Item MultiCrit.Present Value Part II cont. OPC Item MultiCrit.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable \ \ X X X States Commands on OPC Item Neural.Present Value OPC Item Neural.
Siemens OPC Object Specifications ID Object Model Description XLS-0110 XLS Detector Device Smoke and fire detectors. Building Technologies Part III States Commands on OPC Item Relay1.Present Value OPC Item Relay1.PresentValue Result State 512-Quiet 514-Alarm 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X Alarm X X X X X X X X X X X X States Commands on OPC Item SmokeIon.
Siemens OPC Object Specifications ID Object Model Building Technologies Description States XLS-0110 Commands on OPC Item SmokePhoto.Present Value Part III cont. OPC Item SmokePhoto.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable \ \ X X X States Commands on OPC Item Thermal.Present Value OPC Item Thermal.
Siemens OPC Object Specifications ID Object Model Description XLS-0120 XLS HCP Device Intelligent control point, capable of switching on and supporting a notification appliance circuit, telephone, or speaker zone that is remotely located near a detector loop.
Siemens OPC Object Specifications ID Object Model Description XLS-0130 XLS HTRI Device Addressable interface module. Building Technologies Part I States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal X 2-Alarm 1-Normal Alarm X 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled 4 - Enable 5 - Disable \ \ X X States Commands on OPC Item Switch1.Present Value OPC Item Switch1.
Siemens OPC Object Specifications ID Object Model Building Technologies Description States XLS-0130 Commands on OPC Item Switch2.Present Value Part I cont. OPC Item Switch2.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable \ \ X X X States Commands on OPC Item Switch3.Present Value OPC Item Switch3.
Siemens OPC Object Specifications ID Object Model Description XLS-0130 XLS HTRI Device Addressable interface module. Building Technologies Part II OPC Item Switch4.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault X 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable \ \ X X States Commands on OPC Item Relay1.Present Value OPC Item Relay1.
Siemens OPC Object Specifications ID Object Model Building Technologies Description States XLS-0130 Commands on OPC Item Relay2.Present Value Part II cont. OPC Item Relay2.PresentValue Result State 512-Quiet 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X 514-Alarm Alarm X X X 515-Fault Fault X X X 267-Non Default Mode Disabled X X 268-Trouble Bypass Enabled X X X X States Commands on OPC Item Relay3.Present Value OPC Item Relay3.
Siemens OPC Object Specifications ID Object Model Description XLS-0130 XLS HTRI Device Addressable interface module. Building Technologies Part III States Commands on OPC Item Relay4.Present Value OPC Item Relay4.PresentValue Result State 512-Quiet 514-Alarm 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X Alarm X X X X X X X X X X OPC DA Specifications_V3.0_XLS.
Siemens OPC Object Specifications ID Object Model Description XLS-0140 XLS HTRI Relay Device Addressable interface module with relay output.
Siemens OPC Object Specifications ID Object Model Building Technologies Description States XLS-0140 Commands on OPC Item Switch2.Present Value Part I cont. OPC Item Switch2.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable \ \ X X X States Commands on OPC Item Relay1.Present Value OPC Item Relay1.
Siemens OPC Object Specifications ID Object Model Description XLS-0140 XLS HTRI Relay Device Addressable interface module with relay output. Building Technologies Part II States Commands on OPC Item Relay2.Present Value OPC Item Relay2.PresentValue Result State 512-Quiet 514-Alarm 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X Alarm X X X X X X X X X X OPC DA Specifications_V3.
Siemens OPC Object Specifications ID Object Model Description XLS-0150 XLS HUB4 Module Module for serial communication interface (modem or RS485). Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 29 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0160 XLS HUB4 Port Device Serial communication port for HUB-4 module. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 30 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0170 XLS LED Device Indicator LED. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal X 2-Alarm 1-Normal Alarm X 3-Fault 1-Normal Fault X 267-Non Default Mode 12-Disabled Disabled 4 - Enable 5 - Disable \ \ X States Commands on OPC Item LED.Present Value OPC Item LED.
Siemens OPC Object Specifications ID Object Model Description XLS-0180 XLS Manual Station Device Manual pull station. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal X 2-Alarm 1-Normal Alarm X 3-Fault 1-Normal Fault X 267-Non Default Mode 12-Disabled Disabled 4 - Enable 5 - Disable \ \ X States Commands on OPC Item Switch1.Present Value OPC Item Switch1.
Siemens OPC Object Specifications ID Object Model Building Technologies Description States XLS-0180 cont. Commands on OPC Item Switch2.Present Value OPC Item Switch2.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable \ \ X OPC DA Specifications_V3.0_XLS.
Siemens OPC Object Specifications ID Object Model Description XLS-0190 XLSOCM-16 Module Module that provides solid-state relay outputs at locations that are remote from a node's central enclosure Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled \ \ \ \ X X OPC DA Specifications_V3.0_XLS.
Siemens OPC Object Specifications ID Object Model Description XLS-0200 XLS Network Interface Module Network interface card which provides XNET/HNET and CAN network communication within and between enclosures nodes. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 35 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0210 XLS PMI Module Control panel module. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 36 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0220 XLS Panel XLS panel node. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0 - Quiet 1-Normal 2 - Alarm 3 - Fault 267-Non Default Mode 4 - Connect 5 - Disconnect Normal X X 1-Normal Not Reachable X X 1-Normal Security X X 12-Disabled Disconnected X X OPC DA Specifications_V3.0_XLS.xlsx \ \ Page 37 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0230 XLS Port Device Parallel and serial ports. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 38 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0240 XLS Power Module Primary and extender power supply. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 267-Non Default Mode 6 - Activate 7 - Deactivate Normal X X 1-Normal Fault X X 1-Normal Security X X OPC DA Specifications_V3.0_XLS.xlsx \ \ Page 39 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0250 XLS Power Supply Submodule Primary and extender power supply submodules. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 40 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0260 XLS Printer Module Remote printer module which processes one parallel port and two serials ports. Building Technologies States Commands on OPC Item Mode OPC Item Mode OPC Item PresentValue Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 41 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0270 XLS Pseudo Device Non-existing device used for logic function purposes only. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault 22-Supervisory 1-Normal Supervisory 267-Non Default Mode 1-Normal Security 268-Non Default Mode 12-Disabled Disabled OPC DA Specifications_V3.0_XLS.xlsx \ \
Siemens OPC Object Specifications ID Object Model Description XLS-0280 XLS Pseudo Module Non-existing module used for logic function purposes only. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 1-Normal Disabled OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 43 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0290 XLS Relay Output Device Programmable relay element. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X 1-Normal Alarm X X X 1-Normal Fault X X X 1-Normal Disabled X X X States Commands on OPC Item Relay1.
Siemens OPC Object Specifications ID Object Model Description XLS-0300 XLS Switch Input Device Module for input supervision which makes the element addressable to a FireFinder XLS node.
Siemens OPC Object Specifications ID Object Model Description XLS-0310 XLS Unidentified Unidentified event object. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault 22-Supervisory 1-Normal Supervisory 267-Non Default Mode 1-Normal Security 268-Non Default Mode 12-Disabled Disabled OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 46 of 51
Siemens OPC Object Specifications ID Object Model Description XLS-0320 XLS VESDA Device VESDA devices used for smoke detection with continuous air sampling. Building Technologies Part I States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal X 2-Alarm 1-Normal Alarm X 3-Fault 1-Normal Fault X 22-Supervisory 1-Normal Supervisory 267-Non Default Mode 1-Normal Disabled 4 - Enable 5 - Disable \ \ X X States Commands on OPC
Siemens OPC Object Specifications ID Object Model Building Technologies Description States XLS-0320 Commands on OPC Item Alert.Present Value Part I cont. OPC Item Alert.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable \ \ X X X States Commands on OPC Item Fire1.Present Value OPC Item Fire1.
Siemens OPC Object Specifications ID Object Model Description XLS-0320 XLS VESDA Device VESDA devices used for smoke detection with continuous air sampling. Building Technologies Part II States Commands on OPC Item Fire2.Present Value OPC Item Fire2.PresentValue Result State 512-Quiet Normal X 514-Alarm Alarm X 515-Fault Fault 267-Non Default Mode Disabled 268-Trouble Bypass Enabled 4 - Enable 5 - Disable \ \ X X X States Commands on OPC Item Scan.
Siemens OPC Object Specifications ID Object Model Description XLS-0330 XLS VPM VESDA peripheral module. Building Technologies States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault OPC DA Specifications_V3.0_XLS.xlsx \ \ \ \ Page 50 of 51
Siemens Building Technologies Siemens Industry Inc. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000 © Siemens Industry Inc. 2017 Technical specifications and availability subject to change without notice.