Data Sheet for Product

OPC Object Specifications
Siemens
Smart Infrastructure
ID Object Model
Description
XNET-0360
XNET Switch Input Device
OPC Item PresentValue
OPC Item Mode Result State 4 - Enable 5 - Disable \ \
0-Quiet 1-Normal Normal X X
2-Alarm 1-Normal Alarm X X
3-Fault 1-Normal Fault X X
22-Supervisory 1-Normal Supervisory X X
267-Non Default Mode 1-Normal Security X X
268-Non Default Mode 12-Disabled Disabled X X
Result State 4 - Enable 5 - Disable \ \
Normal X X
Alarm X X
Fault X X
Disabled X X
Enabled X X
States
OPC Item Switch1.PresentValue
512-Quiet
514-Alarm
515-Fault
267-Non Default Mode
Module for input supervision which makes the element addressable to a FS20 Modular
node.
States
Commands on OPC Item Mode
Commands on OPC Item Switch1.Present Value
268-Trouble Bypass
OPC DA Specifications_V5.1_FS20_Modular.xlsx Page 44 of 53