Data Sheet for Product
OPC Object Specifications
Siemens
Smart Infrastructure
ID Object Model Description
CS11-0180
CC11 Fire Detector
OPC Item PresentValue
OPC Item Mode Result State 0-Disable 1-Enable \ \
0-Quiet 1-Normal Normal
X
3-Fault 1-Normal Fault
X
10-Test Active 2-Test Test
X
16-Abnormal 1-Normal Abnormal
X
267-Non Default Mode 0-Disabled Disabled
X
6-Not Ready 0-Disabled Not Ready
X
7-Active 1-Normal Activated
X
Logical channels used in the detection domain for fire detection.
States
Commands on OPC Item Mode
OPC DA Specifications_V5.1_CS11.xlsx Page 20 of 33