User Manual
OPC Object Specifications_1
Siemens
Building Technologies
ID Object Model
Description
FS20UL-0140
FS20UL Extinguishing Zone
OPC Item PresentValue
OPC Item Mode Result State 0-Disable 1-Enable 2-Test 14-Normal
0-Quiet 1-Normal Normal
X X
259-Extinguishing Released 1-Normal Extinguishing Released
X X
2-Alarm 1-Normal Alarm
X X
1-Pre Alarm 1-Normal Pre Alarm
X X
7-Active 1-Normal Activated
X X
3-Fault 1-Normal Fault
X X
16-Abnormal 1-Normal Anomaly
X X
6-Not Ready 1-Normal Not Ready
X X
268-Trouble Bypass 0-Disabled Disabled
X X X
267-Non Default Mode 2-Test Test
X X
267-Non Default Mode 285-Walktest Walktest
X X X
The Extinguishing Zone handles the raw alarm information related to extinguishing sensors.
Commands on OPC Item Mode
States
OPC DA Specifications_V3.0_FS20UL.xlsx Page 16 of 40