OPC Interface Specifications Version 3.0 FS20UL Document No.
Siemens Building Technologies FS20UL Fire Panel This workbook describes the objects provided by the Siemens OPC Data Access Server to represent the FS20UL fire control unit Legend ID Object Model Description
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0010 FS20UL Alarm Control Individual entity of control logic for alarm handling. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 267-Non Default Mode 2-Test Test X 7-Active 1-Normal Activated X 3-Fault 1-Normal Fault X 0-Disable 1-Enable X X OPC DA Specifications_V3.0_FS20UL.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0020 FS20UL Alarm Control Group The Alarm Control Group is the means for organizing specific alarm controls . Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 258-Controls Off 265-Controls On 259-Sounders Off 266-Sounders On X X X X OPC DA Specifications_V3.0_FS20UL.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0030 FS20UL Alert Evac Sounders Evacuation sounders used in the Control domain.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0040 FS20UL Alert Sounders Sounders used in the Control domain.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0050 FS20UL Area Off Fire Controls This switches on or off the Fire Controls programmed in the related Area. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 258-Controls Off 265-Controls On \ \ X X OPC DA Specifications_V3.0_FS20UL.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0060 FS20UL Area Off Rts This switches on or off the Remote Transmissions programmed in the related Area. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 258-Controls Off 265-Controls On \ \ X X OPC DA Specifications_V3.0_FS20UL.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0070 FS20UL Area Off Sounders This switches on or off the Audible Souders programmed in the related Area. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 259-Sounders Off 266-Sounders On \ \ X X OPC DA Specifications_V3.0_FS20UL.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0080 FS20UL BACnet Device BACnet device. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State \ \ OPC DA Specifications_V3.0_FS20UL.xlsx \ \ Page 10 of 40
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0090 FS20UL Bypassable Elem Bypassable elements mostly used in the control domain. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 3-Fault 1-Normal Fault X 7-Active 1-Normal Activated X 0-Disable 1-Enable \ \ X X OPC DA Specifications_V3.0_FS20UL.
Siemens Building Technologies OPC Object Specifications_1 ID FS20UL-0100 Object Model FS20UL Digital Input Description Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 3-Fault 1-Normal Fault X 16-Abnormal 1-Normal Anomaly X 0-Disable 1-Enable \ \ X X
Siemens Building Technologies OPC Object Specifications_1 ID FS20UL-0110 Object Model FS20UL Digital Output Description Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0120 FS20UL Evac Control Individual entity of the control logic related to evacuation.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0130 FS20UL Evac Sounders Evacuation sounder channel. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 7-Active 1-Normal Activated X 3-Fault 1-Normal Fault X X 16-Abnormal 1-Normal Anomaly X X 0-Disable 271-Activate Evac X X X 1-Enable 276-Deactivate X X OPC DA Specifications_V3.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0140 FS20UL Extinguishing Zone The Extinguishing Zone handles the raw alarm information related to extinguishing sensors.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0150 FS20UL Fire Control Group The Fire Control Group is the means for organizing the different kinds of fire controls. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 0-Disable 1-Enable X 2-Test 14-Normal X X OPC DA Specifications_V3.0_FS20UL.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0160 FS20UL Fire Detector Logical channels used in the detection domain for fire/smoke detection and technical alarms.
Siemens Building Technologies OPC Object Specifications_1 ID FS20UL-0170 Object Model FS20UL Fire Subsystem Zone Description The Fire Subsystem Zone handles the raw alarm information related to different sensor types.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0180 FS20UL Generic Control Individual entity of the control logic. Each Control has a dedicated functionality.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description Input Channels exclusively used in the logical domain. Specific sensors handle the different FS20UL-0190 FS20UL Generic Digital Input information from the detection devices and a logical input is used for technical alarms coming from other systems.
Siemens Building Technologies OPC Object Specifications_1 ID FS20UL-0200 Object Model FS20UL Generic Element Description Generic Configuration Element. This element is a member of the operation tree and is mainly used for the configuration of country-specific operations and view peripherals.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0210 FS20UL Manual Pull Station Logical channels used in the detection domain for fire detection.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0220 FS20UL Manual Zone The Manual Zone handles the raw alarm information coming from manual call point.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0230 FS20UL Multi State Value Panel and Area multistate objects for block commands. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 2-Block Ack 3-Block Reset 4-Block Silence 5-Block Unsillence 2-Acknowledge X X X X 3-Reset X X X X 4-Silence X X X X 5-Unsilence X X X X OPC DA Specifications_V3.0_FS20UL.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0240 FS20UL Notification Class BACnet notification class. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State \ \ OPC DA Specifications_V3.0_FS20UL.xlsx \ \ Page 26 of 40
Siemens Building Technologies OPC Object Specifications_1 ID FS20UL-0250 Object Model FS20UL Output Description Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description An entire FS20 host (panel or terminal) with respect to the process information. In addition, a FS20UL-0260 FS20UL Panel BACnet Device object is associated so that each host can be addressed as an individual node in the BACnet inter-network.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description The PMI Visibility elements are attached to the PMI Config element which models the local FS20UL-0270 FS20UL Pmi Visibility PMI of an FS20 station. The subordinate Visibility elements are mainly used for configuration purposes (manual activation).
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description The PMI Visibility elements are attached to the PMI Config element which models the local FS20UL-0280 FS20UL Pmi Standby Visibility PMI of an FS20 station. The subordinate Visibility elements are mainly used for configuration purposes (automatic fallback).
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0290 FS20UL Sounders Sounder output logical channel.
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0300 FS20UL Physical Device Device in the hardware domain used in the detection loop. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled \ \ OPC DA Specifications_V3.0_FS20UL.xlsx \ \ Page 32 of 40
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0310 FS20UL Verification Elem Counter which influences the alarm equipment and remote transmission. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Activated \ \ OPC DA Specifications_V3.0_FS20UL.xlsx \ \ Page 33 of 40
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description FS20UL-0320 FS20UL Voice Control Group The means for organizing the different kind of voice controls. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 267-Non Default Mode 2-Test Test \ \ OPC DA Specifications_V3.0_FS20UL.xlsx \ \ Page 34 of 40
Siemens Building Technologies OPC Object Specifications_1 ID Object Model Description This is not an Object Model but provides the read-only information about the event state. The FS20UL-0330 FS20UL Event commands event related to the point can require the acknowledge, silence/unsilence and reset commands.
Siemens Building Technologies OPC Object Specifications_2 ID Object Model Description The Zone handles the raw alarm information coming from one or more detectors. Different purpose.
Siemens Building Technologies OPC Object Specifications_2 ID Object Model Description FS20UL-0350 FS20UL Area The Area controls the alarm organization.
Siemens Building Technologies OPC Object Specifications_2 ID Object Model Description FS20UL-0360 FS20UL Area Propagation This switches on or off the Sections and Zones programmed in the related Area.
Siemens Building Technologies OPC Object Specifications_2 FS20UL Section Description The Section can be used to operate a collection of zones in a safe and easy way. It provides the functionality for switching to on, off, fast, and test.
Siemens Building Technologies Siemens Industry Inc. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000 © Siemens Industry Inc. 2017 Technical specifications and availability subject to change without notice.