Data Sheet for Product
OPC Object Specifications_1
Siemens
Smart Infrastructure
ID Object Model Description
FS20UL-0280
FS20UL Pmi Visibility
OPC Item PresentValue
OPC Item Mode Result State
269-Active
276-Deactivate
\ \
0-Quiet 1-Normal Normal
X
3-Fault 1-Normal Fault
7-Active 1-Normal Activated
X
16-Abnormal 1-Normal Anomaly
256-System Fault 1-Normal Fault
States
Commands on OPC Item Mode
The PMI Visibility elements are attached to the PMI Config element which models the local PMI
of an FS20 station. The subordinate Visibility elements are mainly used for configuration
purposes (manual activation).
OPC DA Specifications_V5.1_FS20UL.xlsx Page 30 of 47