User Manual

Application Sheet CCG081
Chilled/heated ceiling (4 pipe) with 6-way valve on analog output
DXR2..09-
101A
4 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662231_en--_e_--_10
Application
configuration
Equipment Values/Range Template settings
On-board output Radiant ceiling valve position 1 Chilled; Y20; 0...10 V
Chilled; Y30; 0...10 V
Heating/chilled 2-pipe; Y20; 0...10 V
Heating/chilled 2-pipe; Y30; 0...10 V
Heating/chilled 4-pipe 6-way; Y20; 0...10 V
Heating/chilled 4-pipe 6-way; Y30; 0...10 V
Heating; Y20; 0...10 V
Heating; Y30; 0...10 V
Heating/chilled 4-pipe
6-way; Y20; 0...10 V
KNX PL-Link devices Room operator unit device 1 QMX3.P02, QMX3.P34, QMX3.P36, QMX3.P37,
QMX3.P74
QMX3.P34
Optional
configuration
Equipment Values/Range Template settings
On-board output Radiant ceiling valve position 2 Chilled; Y20; 0...10 V
Chilled; Y30; 0...10 V
Heating/chilled 2-pipe; Y20; 0...10 V
Heating/chilled 2-pipe; Y30; 0...10 V
Heating/chilled 4-pipe 6-way; Y20; 0...10 V
Heating/chilled 4-pipe 6-way; Y30; 0...10 V
Heating; Y20; 0...10 V
Heating; Y30; 0...10 V
Heating/chilled 4-pipe
6-way; Y30; 0...10
On-board input
Presence detector 2 (D2
a
)
X1, Normally open
Window contact (D1) D1; Normally closed
Condensation monitor (D3.1, D3.2) X2; Normally closed
KNX PL-Link devices Sensor device 1…4 (D2) UP 258D12
Default values
Parameter Values/Range Template settings
Temperature setpoints Cooling setpoint for Comfort 0 … 50 °C 24 °C
Delta cooling setpoint for Pre-comfort 0 … 10 K 1 K
Cooling setpoint for Economy 0 … 50 °C 35 °C
Cooling setpoint for Protection 0 … 50 °C 40 °C
Heating setpoint for Comfort 0 … 50 °C 21 °C
Delta heating setpoint for Pre-comfort 0 … 10 K 1 K
Heating setpoint for Economy 0 … 50 °C 15 °C
Heating setpoint for Protection 0 … 50 °C 12 °C
Radiant ceiling Enable condensation monitor input Yes, No Yes
Chilled ceiling valve pos. for value
X1
0 … 100 % 0 %
Chilled ceiling valve pos. for value
Y1
0 … 100 % 50 %
Chilled ceiling valve pos. for value
X2
0 … 100 % 100 %
Chilled ceiling valve pos. for value
Y2
0 … 100 % 0 %
Ceiling heating valve pos. for value
X1
0 … 100 % 0 %
Ceiling heating valve pos. for value
Y1
0 … 100 % 50 %
Ceiling heating valve pos. for value
X2
0 … 100 % 100 %
Ceiling heating valve pos. for value
Y2
0 … 100 % 100 %