Smart Infrastructure A6V11993473_en_a_51
2021-10-31
Medium or Large KNX Installation without Multicast Routing Between KNX Lines
1)
1)
Multicast address is not supported. The connection between Desigo CC Compact for Electrical
Applications and the KNXnet/IP routers works through the KNXnet/IP tunneling connection only.
KNX Compatibility
● ETS tool versions for KNXPROJ and ESF files:
– ETS 4
– ETS 5.1
– ETS 5.7
● Desigo CC Compact V4.0 or higher
Gamma KNX Compatibility
● Desigo CC Compact V4.1 or higher
SORIS Limits
● SORIS Drivers: maximum of 10 per Desigo CC Compact server; maximum of 10 per
Desigo CC Compact FEP
● SORIS Networks: no limit
● SORIS Adapters: no limit
● Objects: 10,000 per adapter
KNX/IP Routers Configuration Limits
● Maximum number of KNX/IP routers or interfaces per KNX adapter tested: 5
NOTE: Even though there is no technical limitation, for configurations beyond this limit,
contact Customer Support for further evaluation and approval.