Open Integration Platform
Desigo CC is an open system by design and supports a variety of open system proto-
cols and IT standards.
Open System Standard Protocols
BACnet. Certified by BACnet Testing Laboratory as BACnet Advanced Workstation
Software (BTL B-AWS), including support for Life Safety Points and Life Safety
Zones.
OPC Client OLE for Process Control OPC DA 2.0
OPC Server OLE for Process Control OPC DA V2.05/V3.00
Modbus. Supported using PXC controller
XNET. FireFinder XLS and MXL fire safety systems
OnVIF. Standard for IP video camera systems
Axis. Standard for Axis video camera systems
IT Standards
SNMP (V1 and V2). IP device monitoring
WMI. Computer hardware monitoring
SMTP, PO3, IMAP. For email delivery
Microsoft SQL Server. Trend and History data storage
HTTP(S). Client-server communication
DWG, DXF. AutoCAD import formats
TAP. Protocol for pager communication
System Compatibility
APOGEE BACnet (Firmware 3.2.4 through 3.5)
APOGEE P2 Ethernet (Firmware 2.8.10 in PXC, MBC, MEC controllers)
APOGEE P2 RS-485 via AEM (Firmware 2.8 in PXC, MBC, MEC controllers)
FireFinder XLS (MP8, MP10, MP11, MP12)
Siemens MXL (35.06J)
Desigo Fire Safety System (FS20 UL MP1.x, MP2.0, MP2.1, MP2.2)
Desigo Intelligent Voice Communication System (MP2.0, MP2.1, MP2.2)
SiPass Integrated (2.7)
Siveillance VMS50 / 100 / 200 / 200 embedded / 300
(2014 (7.0d), 2016 R3 SP1 (10.2b), 2017 R1 (11.1a), 2017 R2 (11.2a))
Milestone XProtect Essential+, Express+, Professional+, Expert, Corporate
(2014 (7.0d), 2016 R3 SP1 (10.2b), 2017 R1 (11.1a), 2017 R2 (11.2a))
Third-party BACnet (BTL B-AWS)
Third-party OPC Client compliant with OPC DA2.0
Third-party OPC Server compliant with OPC DA V2.05/V3.00
SNMP Manager (V1 and V2)
Simatic S7- 300/400(-H)/1200 V3