Specifications

2/8
Siemens FI 01 · 2015 US Edition
Temperature Measurement
Transmitters for mounting in sensor head
SITRANS TH200 two-wire system, universal
2
Overview
Ultra flexible - with the universal SITRANS TH200 transmitter
Two-wire devices for 4 to 20 mA
Mounting in the connection head of the temperature sensor
Universal input for virtually any type of temperature sensor
Configurable over PC
Benefits
Compact design
Flexible mounting and center hole allow you to select your pre-
ferred type of installation
Electrically isolated
Test sockets for multimeters
Diagnostics LED (green/red)
Sensor monitoring
open circuits and short-circuits
Self-monitoring
Configuration status stored in EEPROM
SIL2 (with Order Code C20), SIL2/3 (with C23)
Expanded diagnostic functions, such as slave pointer, operat-
ing hours counter, etc.
Special characteristic
Electromagnetic compatibility to EN 61326 and NE21
Application
SITRANS TH200 transmitters can be used in all industrial sec-
tors. Due to their compact size they can be installed in the con-
nection head type B (DIN 43729) or larger. The following sen-
sors/signal sources can be connected over their universal input
module:
Resistance thermometers (2, 3 or 4-wire system)
Thermocouples
Resistance-based sensors and DC voltage sources
The output signal is a direct current from 4 to 20 mA in accor-
dance with the sensor characteristic.
Transmitters of the "intrinsically safe" type of protection can be in-
stalled within potentially explosive atmospheres. The devices
comply with the Directive 94/9/EC (ATEX), as well as FM and
CSA regulations.
Function
The SITRANS TH200 is configured over a PC. A USB or RS 232
modem is linked to the output terminals for this purpose. The
configuration data can now be edited using the SIPROM T soft-
ware tool. The configuration data are then permanently stored in
the non-volatile memory (EEPROM).
Once the sensors and power supply have been correctly con-
nected, the transmitter outputs a temperature-linear output sig-
nal and the diagnostics LED displays a green light. In the case
of a sensor short-circuit, the LED flashes red, an internal device
fault is indicated by a steady red light.
The test socket can be used to connect an ammeter at any time
for monitoring purposes and plausibility checks. The output cur-
rent can be read without any interruption, or even without open-
ing the current loop.
SITRANS TH200 function diagram
Input
A/D Analog-digital converter
Sensors Resistance thermometer, thermocouple,
resistance-based sensor, mV sensor
μC1 Microcontroller, secondary circuit
Output
μC2 Microcontroller, primary circuit
D/A Digital-analog converter
U
aux
Auxiliary power supply
I
out
Output current
(1) Electrically isolated
(2) LED
TC/RTD
sensor
(2)
+1
-2
(1)
µC1
µC2
Test
4 ... 20 mA U
aux
, I
out
SITRANS TH200/TH300
D
A
A
D
© Siemens AG 2015