Specifications

2/32
Siemens FI 01 · 2015 US Edition
Temperature Measurement
Transmitters for rail mounting
SITRANS TR200 two-wire system, universal
2
Selection and Ordering data
Article No.
Supply units see Chapter "Supplementary Components".
Ordering example 1:
7NG3032-0JN00-Z Y01+Y17+Y29+U03
Y01: -10 ... +100 °C
Y17: TICA123
Y29: TICA123
Ordering example 2:
7NG3032-0JN00-Z Y01+Y17+Y23+Y29+U25
Y01: -10 ... +100 °C
Y17: TICA123
Y23: TICA123HEAT
Y29: TICA123HEAT
Factory setting:
Pt100 (IEC 751) with 3-wire circuit
Measuring range: 0 … 100 °C (32 … 212 °F)
Fault current: 22.8 mA
Sensor offset: 0 °C (0 °F)
Damping 0.0 s
Temperature transmitter SITRANS TR200
For mounting on a standard DIN rail, two-wire
system, 4 to 20 mA, programmable, with electri-
cal isolation, with documentation on MiniDVD
• Without explosion protection 7NG3032-0JN00
• With explosion protection to ATEX 7NG3032-1JN00
Further designs Order code
Please add "-Z" to Article No. with and specify
Order codes(s).
With test protocol (5 measuring points) C11
Functional safety SIL2 C20
Functional safety SIL2/3 C23
Customer-specific programming
Add "-Z" to Article No. and specify Order code(s)
Measuring range to be set
Specify in plain text (max. 5 digits):
Y01: ... to ... °C, °F
Y01
1)
Measuring point no. (TAG), max. 8 characters Y17
2)
Measuring point descriptor, max. 16 charac-
ters
Y23
2)
Measuring point message, max. 32 characters Y24
2)
Text on front label, max. 16 characters Y29
2)3)
Pt100 (IEC) 2-wire, R
L
= 0 U02
4)
Pt100 (IEC) 3-wire U03
4)
Pt100 (IEC) 4-wire U04
4)
Thermocouple type B U20
4)5)
Thermocouple type C (W5) U21
4)5)
Thermocouple type D (W3) U22
4)5)
Thermocouple type E U23
4)5)
Thermocouple type J U24
4)5)
Thermocouple type K U25
4)5)
Thermocouple type L U26
4)5)
Thermocouple type N U27
4)5)
Thermocouple type R U28
4)5)
Thermocouple type S U29
4)5)
Thermocouple type T U30
4)5)
Thermocouple type U U31
4)5)
With TC: CJC external (Pt100, 3-wire) U41
With TC: CJC external with fixed value, specify
in plain text
Y50
Special differing customer-specific program-
ming, specify in plain text
Y09
6)
Fail-safe value 3.6 mA (instead of 22.8 mA) U36
2)
Accessories Article No.
Modem for SITRANS TH100, TH200, TR200
and TF with TH200 incl. SIPROM T parame-
terization software
7NG3092-8KU
With USB connection
MiniDVD for temperature measuring instru-
ments for
A5E00364512
With documentation in German, English,
French, Spanish, Italian, Portuguese and
SIPROM T parameterization software
1)
For customer-specific programming for RTD and TC, the start value and
the end value of the required measuring span must be specified here.
2)
For this selection, Y01 or Y09 must also be selected.
3)
Text on front plate is not saved in the device.
4)
For this selection, Y01 must also be selected.
5)
Internal cold junction compensation is selected as the default for TC.
6)
For customer-specific programming, for example mV and ohm, the start
value and the end value of the required measuring span and the unit must
be entered here.
© Siemens AG 2015