Home Theater Server User Manual

Chapter 10 - Create/Edit
Common Editor Fields and Buttons
59
Siemens Industry, Inc.
125-3584T
The Object Identifier field in the Web Server user interface shows the two components
separated by a comma.
The following Object Identifier represents a Binary Value object, instance 6:
The Object Identifier field can be left blank on creation, and the controller will
automatically assign an appropriate value.
If you want to enter a specific instance number, you can enter the desired instance
number integer in the Object Identifier field.
For instance, if you want to create a Binary Value object with instance 100, you would
enter the following in the Point Editor Object Identifier:
Upon successful creation of this object, the Object Identifier field will show both
components:
The Object Identifier field cannot be modified after creation.
Object Reference
Some BACnet objects have properties that reference other BACnet objects.
For instance, an Event Enrollment object has a Reference Point field. This field can be
filled by selecting the drop-down arrow, and selecting an object from the list, or by
selecting the ? (question mark) button and manually entering an Object Reference.
The drop-down arrow option:
The ? (question mark) button option:
Manually entering an Object Reference requires entering the instance of the Device
Object containing the desired object, and the Object Identifier of the desired object.
The above picture indicates a reference to a Binary Value object with instance 100, on
a Device with instance 1021.