NOTE:
The overloads are dialed in by the factory, based
on the NEC FLA rating tables, and assume a trip
(activation) level at 125%. If the 125% is
acceptable for your installation, dial in the overload
to match the connected motor's FLA rating. If a
different percentage is desired, a multiplier must be
used to determine the proper setting. This is a two-
step process:
First, determine the multiplier. This can be
calculated by dividing 125% by the desired
percentage.
Formula: Desired % ÷ 125% = Multiplier
Example: 115% ÷ 125% = 0.92
Second, the new multiplier is used with the motor's
FLA to determine the dial setting of the overload.
This can be calculated by multiplying the Motor
FLA by the multiplier to provide the desired setting.
Formula: Motor FLA × multiplier = Dial Setting
Example: 24 × 0.92 = 22.08
Therefore, a motor with an FLA of 24 Amps, and a
desired overload setting of 115% would require the
overload dial to be set to a value of 22.08 to have
the desired effect.
With some high-efficiency motors, the overload
supplied with the bypass option may not be able to
be dialed down low enough for the installation.
When this occurs, an alternate overload relay must
be installed into the bypass option.
When an overload is exchanged in the installation
to a smaller size, the UL certification will remain on
the unit. However, the installation will be subject to
approval by the customer and/or the local electrical
authority.