Data Sheet for Product

BT300 HVAC Drives Electronic Bypass (E-Bypass) Options Submittal Sheet
Document No. 154-129
February 19, 2018
Siemens Industry, Inc. Page 3 of 10
Table 2. E-Bypass Frame Sizes and Power Ranges per NEC Motor Tables.
208
-
240
380
-
500
208
-
240
380
-
500
HP kW Frame Size Output Current
1 0.75
4
4.8
1.5 1.1
4
6.7 3.4
2 1.5 8.0 4.8
3 2.2 11.0 5.6
5 4
5
18.0 9.6
7.5 5.5 24.2 12.0
10 7.5
5
31.0 16.0
15 11
6
48.0 23.0
20 15 62.0 31.0
25 18.5
7 6
75.0 38.0
30 22 88.0 46.0
40 30 105.0 61.0
50 37
8 7
143.0 72.0
60 45 170.0 87.0
75* 55 208.0 105.0
100* 75
9
8
261.0 140.0
125* 90 310.0 170.0
150 110 205.0
200 132
9
261.0
250 160 310.0
*Available for 230 Vac and above.