Installation Instructions
Document No. DPD01375
Installation Instructions
August 24, 2018
Page 34 of 36
Siemens Industry, Inc.
Table 10. Siemens Bypass Class 10 Overload Relay Setting Data – 460 Volt.
HP
kW
Frame
Size
Drive
FLA
NEC
FLA
Overload
Min.
Setting
Min.
%
FLA
Max.
Setting
Max
%FLA
Factory
Setting
1.5
1.1
4
3.4
3.0
2.2
65%
3.2
94%
3.0
2
1.5
4.8
3.4
2.8
58%
4.0
83%
3.4
3
2.2
5.6
4.8
3.5
63%
5
89%
4.8
5
4
9.6
7.6
5.5
57%
8.0
83%
7.6
7.5
5.5
12.0
11.0
11
92%
16
133%
11.0
10
7.5
5
16.0
14
11
69%
16
100%
14
15
11
23.0
21
17
74%
22
96%
21
20
15
31.0
27
23
74%
28
90%
27
25
18.5
6
38.0
34
28
74%
40
105%
34
30
22
46.0
40
28
61%
40
87%
40
40
30
61.0
52
47
77%
59
97%
52
50
37
7
72.0
65
54
75%
75
90%
65
60
45
87.0
77
70
80%
100
92%
77
75
55
105.0
96
50
48%
200
190%
96
100
75
8
140.0
124
50
36%
200
143%
124
125
90
170.0
156
50
29%
200
118%
156
150
110
205.0
180
50
24%
200
98%
180
200
132
9
261.0
240
160
61%
630
241%
240
250
160
310.0
302
160
52%
630
203%
302