Installation Instructions

Document No. DPD01375
Installation Instructions
August 24, 2018
Siemens Industry, Inc.
Page 7 of 36
Figure 5. Conduit Locations for UL Type 1 FS4 through FS7 Bypasses.
Figure 6. Conduit Locations for UL Type 1 FS8 Bypass.
NOTES:
1. Knockout locations have not been provided for the Input and/or Output power connections;
connections are completed by the customer.
2. The Input and Output power connection cannot be in the same conduit.
3. The Input and Output connections must be at least 6 inches away from the control wiring.
4. Locate the Input conduit in the upper right-hand side of the cabinet, and the Output conduit in the
lower right-hand side of the cabinet.