Installation Instructions

Document No. DPD01375
Installation Instructions
August 24, 2018
Page 34 of 36
Siemens Industry, Inc.
Table 10. Siemens Bypass Class 10 Overload Relay Setting Data 460 Volt.
HP
kW
Frame
Size
Drive
FLA
NEC
FLA
Overload
Min.
Setting
Min.
%
FLA
Max.
Setting
Max
%FLA
Factory
Setting
1.5
1.1
4
3.4
3.0
2.2
65%
3.2
94%
3.0
2
1.5
4.8
3.4
2.8
58%
4.0
83%
3.4
3
2.2
5.6
4.8
3.5
63%
5
89%
4.8
5
4
9.6
7.6
5.5
57%
8.0
83%
7.6
7.5
5.5
12.0
11.0
11
92%
16
133%
11.0
10
7.5
5
16.0
14
11
69%
16
100%
14
15
11
23.0
21
17
74%
22
96%
21
20
15
31.0
27
23
74%
28
90%
27
25
18.5
6
38.0
34
28
74%
40
105%
34
30
22
46.0
40
28
61%
40
87%
40
40
30
61.0
52
47
77%
59
97%
52
50
37
7
72.0
65
54
75%
75
90%
65
60
45
87.0
77
70
80%
100
92%
77
75
55
105.0
96
50
48%
200
190%
96
100
75
8
140.0
124
50
36%
200
143%
124
125
90
170.0
156
50
29%
200
118%
156
150
110
205.0
180
50
24%
200
98%
180
200
132
9
261.0
240
160
61%
630
241%
240
250
160
310.0
302
160
52%
630
203%
302