Data Sheet for Product

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Submittal Sheet
Document No. 154-128
February 19, 2018
Siemens Industry, Inc. Page 9 of 10
Specification Description
Auxiliary output
10 Vdc ±3%, 10 mA (short-circuit protected)
24 Vdc ±10%, 250 mA (short-circuit protected)
Embedded Protocols
RS-485:
APOGEE P1, BACnet MS/TP, Modbus RTU, Metasys N2
Ethernet:
BACnet IP, Modbus TCP
Protection features
Under-voltage trip limit
Over-voltage trip limit
Ground fault protection
Input (mains) supervision
Motor phase supervision
Over-current protection
Unit over-temperature protection
Motor overload protection
Motor stall protection
Motor underload protection
Short-circuit protection of 10 Vdc and 24 Vdc reference voltages
Table 4. Accessories.
Accessory Description
Frame Size
4 5 6
EMC Filter Kit BT300-EMCKIT-FS4 BT300-EMCKIT-FS5 BT300-EMCKIT-FS6
Accessory Description
Frame Size
7 8 9
EMC Filter Kit BT300-EMCKIT-FS7 N/A BT300-EMCKIT-FS9
Part Number Description
BT300-DIAGBD-BTC Conventional Bypass Diagnostic Board
Table 5. Dimensions in Inches (Millimeters).
Frame
Size
Height Width Depth
FS4 35 (901)
7 (173)
10 (256)
FS5 44 (1,120) 11 (288)
FS6 55 (1,391) 9 (224) 12 (302)
FS7 59 (1,486) 14 (368) 13 (323)
FS8 48 (1,219) 36 (914) 17 (426)
FS9 72 (1,830) 48 (1,221) 25 (640)