Data Sheet for Product
Table Of Contents
Submittal Sheet
Document No. 154-128
February 19, 2018
BT300 HVAC Drives Conventional
Bypass (C-Bypass) Options
Siemens Industry, Inc.
Description
The BT300 Conventional Bypass (C-Bypass) is a
companion package for the family of BT300 HVAC
Drives.
For information on the family of BT300 HVAC Drives,
see the BT300 HVAC Drives Submittal Sheet
(154-126) and BT300 HVAC Drives Technical
Specification Sheet (149-711).
BT300 C-Bypass Features
• Bypass Start-up Wizard
• Diagnostic board with test points
• Control logic short circuit protection
• 100,000 AIC short circuit rating
• Country of Origin (COO) USA
• IBC 2012 Seismic Certified
• OSHPD Certified
• Compact design
C-Bypass Power Features
2-Contactor: Output and Bypass
• Overload protection in bypass mode
• Electrically and mechanically interlocked
Drive Isolation
• Drive Service Switch allows the drive to be
disconnected from power during troubleshooting
without disrupting bypass operation.
• Optional 3-Contactor (Drive Input)
− Contactors electrically interlocked.
− Drive test function
− Complete electrical isolation of drive
Input Device
• Disconnect with fuses.
• (Optional) Circuit breaker.
• All doors are interlocked and can be
secured with a padlock.
5% Input Impedance
• Internal reactors lower harmonics that the drive
produces.
• BT300 C-Bypass requires no additional input reactors
Reactor Options
• Line reactor (in NEMA 1 enclosure) supplied separately.
• Load reactor (in NEMA 1 enclosure) supplied separately.
C-Bypass Control Features
• Enable Input
Generally used for safety tie-ins; the motor will not
operate the drive or bypass when open.
• Common Remote Start/Stop
Common remote start/stop can be used in both drive and
bypass mode.
• Essential Services Mode
− Typically used for smoke purge; the motor goes to
bypass regardless of the selected mode.
− No call to stop will have an effect, including open
safety or stop commands.
− Only turning the power off or opening this contact
will stop the motor.
C-Bypass – Door Mounted Control Devices
• Drive-Off-Bypass selector
• Bypass pilot light
• Drive Test on/off selector (with third Contactor)