Basic Documentation

Disclaimer: These are sample drawings and sequences. Designers are responsible for
finalizing the content for their particular projects.
3. Qualifications:
a. VFDs and options shall be UL508 and cUL listed as a complete assembly.
The base VFD shall be UL listed for 100 kA SCCR.
b. The base VFD shall conform to the European Union Electromagnetic
Compatibility directive and CE requirement. The VFD shall meet EN
61800-3 for the First Environment restricted level (Category C2).
c. All enclosures, Type 12, Type 1 or Type 12 with an integral disconnect
shall have the same footprint.
K. Submittals
1. Submittals shall include the following information:
2. Outline dimensions, conduit entry location and weights
3. Customer connection and power wiring diagrams
4. Complete technical product description include a complete list of options
provided
5.
L. Installation
1. Installation shall be the responsibility of the mechanical contractor. The
contractor shall install the drive in accordance with the recommendations of the
VFD manufacturer as outlined in the installation manual.
2. The electrical contractor shall complete power wiring. The contractor shall
complete all wiring in accordance with the recommendations of the VFD
manufacturer as outlined in the installation manual.
M. Start-up
1. Certified factory start-up shall be provided for each drive by a factory authorized
service center. A certified start-up form shall be filled out for each drive with a
copy provided to the owner, and a copy kept on file at the manufacturer.
N. Product Support
1. Factory trained application engineering and service personnel that are thoroughly
familiar with the BT300drive products offered will be locally available at both the
specifying and installation locations.
O. Warranty