17. Two safety inputs shall be available for customer connecting. If either of these inputs opens, the
electronic bypass will not operate the motor in bypass or drive mode. These inputs are typically used
for such things as fire alarm and freeze stat.
Part 3 – EXECUTION
3.01 Installation
A. Installation shall be the responsibility of the mechanical contractor. The contractor shall install the drive in
accordance with the recommendations of the VFD manufacturer as outlined in the installation manual.
B. The electrical contractor shall complete power wiring. The contractor shall complete all wiring in
accordance with the recommendations of the VFD manufacturer as outlined in the installation manual.
3.02 Start-Up
A. Certified factory start-up shall be provided for each drive by a factory authorized service center. A certified
start-up form shall be filled out for each drive with a copy provided to the owner, and a copy kept on file at
the manufacturer.
3.03 Product Support
A. Factory-trained application engineering and service personnel that are thoroughly familiar with the BT300
drive products offered will be locally available at both the specifying and installation locations.
3.04 Warranty
A. Warranty shall be 18 months from date of manufacture, or 36 months from the date of manufacture with
certified start-up.
END OF SECTION