Basic Documentation

Page 2 of 9 Siemens Building Technologies, Inc.
Document No. A6V10431169
All printed circuit boards shall be completely tested and burned-in before being assembled into the completed VFD. All
testing and manufacturing procedures shall be ISO 9001 certified. Test reports for each drive supplied shall be available
upon delivery.
C. Qualifications:
VFDs and options shall be UL508 and cUL listed as a complete assembly. The base VFD shall be UL listed for 100 kA SCCR.
The VFD assembly including bypass if specified, shall be seismically certified and labeled in accordance with the 2012
International Building Code (IBC).
The base VFD shall conform to the European Union Electromagnetic Compatibility directive and CE requirement. The VFD
shall meet EN 61800-3 for the First Environment restricted level (Category C2).
All enclosures, UL Type 1 and Type 12 (with or without an integral disconnect) shall have the same footprint.
D. Submittals
Submittals shall include the following information:
Outline dimensions, conduit entry location and weights
Customer connection and power wiring diagrams
Complete technical product description include a complete list of options provided
Part 2 - Products
2.01 Variable Frequency Drives
The Variable Frequency Drives (VFDs) shall be solid state, with 6-Pulse Width Modulation (PWM) output. The VFD package
as specified herein shall be enclosed in a Type 1 enclosure, completely assembled and tested by the manufacturer. The VFD
shall employ a full wave rectifier (to prevent input line notching), capacitors, and Insulated Gate Bipolar Transistors (IGBT’s)
as the output-switching device. The drive efficiency shall be 97% or better at full speed and full load. Displacement power
factor shall be no less than 0.98 at all speeds and loads.
All VFD provided shall have the following:
Input voltage 208-240, 380-480 +/- 10% of the nominal voltage.
VFDs shall be capable of continuous full load operation under the following conditions
Voltage tolerance + or 10% of specified line voltage.
Output Frequency 0 to 150 Hz. Operation above 60 Hz shall require programming changes to prevent
inadvertent high-speed operation.
Environmental operating conditions: 0 to 40°C, 0 to 1000 meters above sea level, less than 95% humidity, non-
condensing.
Enclosure shall be rated UL Type enclosures or as specifically mentioned elsewhere.