Installation Instructions
Installation Instructions
Document No. DPD01589
May 8, 2014
Page 2 of 12
FS04 EMC Kit Installation
FS04 Parts List
Item
Description
Qty
1
0.18 Diameter Clamp
1
2
0.25 Diameter Clamp
1
3
Intermediate Wire Tie
5
4
M5 x 16mm Screw
1
1. Line Power Cabling: No special requirements.
2. Motor Power Cabling:
A. Loop grounding clamp (Item 2) to fit 14 AWG VFD style cable and fasten
to foot with Item 4. Ref Americable Part Number 37-108.
B. Shield is to be connected to the motor via an EMC style conductive gland
or of the like.
3. Control cabling:
A. Loop grounding clamps (Item 1) to fit 8 conductor 22 AWG control cable.
Ref. Belden Part Number 9944. For other cable sizes, see Keystone
Electronics Part Numbers 8100-8113.
B. Use existing grounding lamella furnished with bypass to properly connect
shield of control wiring to drive earthing plate.
4. Install Item 3 to control wiring as required to ensure adequate wire separation to
power wiring.