Installation Instructions

Installation Instructions
Document No. DPD01589
May 8, 2014
Page 6 of 12
FS06 EMC Kit Installation
FS06 Parts List
Item
Description
Qty
1
0.18 Diameter Clamp
1
2
0.75 Diameter Clamp
1
3
Small Clamshell Toroid
3
4
Large Clamshell Toroid
2
5
Input Filter
1
6
Filter Enclosure
1
7
Intermediate Wire Tie
5
8
M5 x 16mm Screw
1
1. Line Power Cabling:
A. Maximum load side cable length from input filter to bypass input
device not to exceed 48.0".
B. Ensure ground connection is employed between load side of filter
and bypass input ground terminal.
2. Motor Power Cabling:
A. Loop grounding clamp (Item 2) to fit 4 AWG VFD style cable. Ref.
Americable Part Number 37-108.
B. Shield is to be connected to the motor via an EMC style
conductive gland or of the like.
3. Control Cabling:
A. Loop grounding clamps (Item 1) to fit 8 conductor 22 AWG
control cable. Ref. Belden Part Number 9944. For other cable sizes, see
Keystone Electronics Part Numbers 8100-8113.
B. Use existing grounding lamella furnished with bypass to properly
ground control wiring to drive earthing plate.
4. Install Item 7 to control wiring as required to ensure adequate wire
separation to power wiring.