Installation Instructions
Installation Instructions
Document No. DPD01589
May 8, 2014
Page 4 of 12
FS05 EMC Kit Installation
FS05 Parts List
Item
Description
Qty
1
0.18 Diameter Clamp
1
2
0.44 Diameter Clamp
1
3
Toroid Assembly
1
4
Small Clamshell Toroid
5
5
Intermediate Wire Tie
5
6
M5 x 16mm Screw
1
1. Line Power Cabling:
A. Cabling to pass thru Item 3 prior to connecting to bypass input device.
2. Motor Power Cabling:
A. Loop grounding clamp (Item 2) to fit 8 AWG VFD style cable. Ref.
Americable Part Number 37-108.
B. Shield is to be connected to the motor via an EMC style conductive gland
or of the like.
3. Control Cabling:
A. Loop grounding clamps (item 1) to fit 8 conductor 22 AWG control cable.
Ref. Belden Part Number 9944. For other cable sizes, see Keystone
Electronics Part Numbers 8100-8113.
B. Use existing grounding lamella furnished with bypass to properly connect
shield of control wiring to drive earthing plate.
4. Install Item 5 to control wiring as required to ensure adequate wire separation to
power wiring.