Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Application Siemens Industry, Inc. • 83
24-hour support +1-800-877-7545 (Dial 2)
3
Figure 24. Stall characteristics settings.
Stall time limit (P3.9.13)
This time can be set between 1.0 and 120.0s.
This is the maximum time allowed for a stall stage. The stall time is counted by an internal up/down
counter.
If the stall time counter value goes above this limit, the protection will cause a trip (see P3.9.11). See
page 49.
Figure 25. Stall time count.
Underload protection: Field weakening area load (P3.9.16)
The torque limit can be set between 10.0-150.0% x T
nMotor
.
This parameter gives the value for the minimum torque allowed when the output frequency is above the
field weakening point. See Figure 26.
If you change parameter P3.1.1.4 (Motor nominal current), this parameter is automatically restored to
the default value. See page 52.
f
I
Par. P3.9.12
Par. P3.9.14
11100.emf
Stall area
Par. P3.9.13
11101.emf
Tr i p ar ea
Ti m e
St al l t i m e coun t er
St al l
No stall
Tr i p / w a r n i n g
par. P3.9.11