Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Industry, Inc. • 52 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
3.5.12 Group 3.10: Automatic reset
Table 40: Autoreset Settings.
Code Parameter Min Max Unit Default ID Description
P3.10.1 Automatic reset 0 1 0 731
0 = Disabled
1 = Enabled
P3.10.2 Restart function 0 1 1 719
The start mode for Automatic
reset is selected with this
parameter:
0 = Flying start
1 = According to par. P3.2.4
P3.10.3 Wait time 0,10 10000,0 s 0,50 717
Wait time before the first
reset is executed.
P3.10.4 Trial time 0,00 10000,0 s 60,00 718
When the trial time has
elapsed, and the fault is still
active, the drive will trip to
fault.
P3.10.5 Number of trials 1 10 4 759
NOTE: Total number of trials
(irrespective of fault type)
P3.10.6
Auto-reset:
Under-voltage
0 1 1 720
Auto-reset permitted?
0 = No
1 = Yes
P3.10.7
Auto-reset:
Over-voltage
0 1 1 721
Auto-reset permitted?
0 = No
1 = Yes
P3.10.8
Auto-reset:
Over-current
0 1 1 722
Auto-reset permitted?
0 = No
1 = Yes
P3.10.9 Auto-reset: AI low 0 1 1 723
Auto-reset permitted?
0 = No
1 = Yes
P3.10.10
Auto-reset: Unit over-
temperature
0 1 1 724
Auto-reset permitted?
0 = No
1 = Yes
P3.10.11
Auto-reset: Motor
overtemperature
0 1 1 725
Auto-reset permitted?
0 = No
1 = Yes
P3.10.12
Auto-reset:
External fault
0 1 0 726
Auto-reset permitted?
0 = No
1 = Yes
P3.10.13
Auto-reset:
Underload fault
0 1 0 738
Auto-reset permitted?
0 = No
1 = Yes