Siemens Application Siemens Industry, Inc. • 43
24-hour support +1-800-877-7545 (Dial 2)
3
P3.5.2.29 AI5 custom. max -160.00 160.00 % 100.00 192 Custom range max setting
P3.5.2.30 AI5 signal inversion 0 1 0 198
0 = Normal
1 = Signal inverted
P3.5.2.31 AI6 signal selection
AnIN
Slot0.1
199
See P3.5.2.13. Programma-
ble
P3.5.2.32 AI6 signal filter time 0.00 300.00 s 1.0 200 See P3.5.2.14.
P3.5.2.33 AI6 signal range 0 1 0 201
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P3.5.2.34 AI6 custom. min -160.00 160.00 % 0.00 202 See P3.5.2.16.
P3.5.2.35 AI6 custom. max -160.00 160.00 % 100.00 203 See P3.5.2.17.
P3.5.2.36 AI6 signal inversion 0 1 0 209 See P3.5.2.18.
Table 30: Analog input settings.
Code Parameter Min Max Unit Default ID Description