Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
75 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.7.1
Range 1 Low Lim
Hz
0
320
0
509
Defines the low limit of the first
prohibited frequency. The drive
will change its accel/decel time by
the RampTimeFactor (P3.7.7)
while within the range of this low
limit and the Range 1 High Lim
(P3.7.2).
NOTE: The drive will not control
within these ranges, it will either
be faster or slower, but never
within the range defined.
P3.7.2
Range 1 High Lim
Hz
0
320
0
510
Defines the high limit of the first
prohibited frequency. The drive
will change its accel/decel time by
the RampTimeFactor (P3.7.7)
while within the range of this high
limit and the Range 1 Low Lim
(P3.7.1).
NOTE: The drive will not control
within these ranges; it will either
be faster or slower, but never
within the range defined.
P3.7.3
Range 2 Low Lim
Hz
0
320
0
511
Defines the low limit of the
second prohibited frequency. See
Range 1 Low Lim (P3.7.1) for
further details.
P3.7.4
Range 2 High Lim
Hz
0
320
0
512
Defines the high limit of the
second prohibited frequency. See
Range 1 High Lim (P3.7.2) for
further details.
P3.7.5
Range 3 Low Lim
Hz
0
320
0
513
Defines the low limit of the third
prohibited frequency. See Range
1 Low Lim (P3.7.1) for further
details.
P3.7.6
Range 3 High Lim
Hz
0
320
0
514
Defines the high limit of the third
prohibited frequency. See Range
1 High Lim (P3.7.2) for further
details.
P3.7.7
RampTimeFactor
0.1
10
1
518
Defines the multiplier of the
currently selected ramp time
(accel time 1/2 and decel time
1/2) between the prohibited
frequency limits.