Operating Instructions

Training Exercises
10
Exercise Answers/Information
43
Siemens Industry, Inc. 125-1007 Rev.BA
2014-08-14
Ramp Times
Accel = 6s
Set Accel Time 1 (3.4.2) to 6
Decel = 3s
Set Decel Time 1 (3.4.3) to 3
Start/Stop Types
Flying Start
Set Start Function (3.2.4) to Flying Start
NOTE:
This is configured using the Startup Wizard.
Coast to Stop
Set Stop Function (3.2.5) to Coasting
NOTE:
This is configured using the Startup Wizard.
Auto Reset
Enable
Set Automatic Reset (3.10.1) to Enabled
Undervoltage Fault
Set Undervoltage Flt (3.10.6) to Yes
Wait 2s
Set Wait Time (3.10.3) to 2
Try 5 times in 80s timeline
Set Trial Time (3.10.4) to 80
Set Number of Trials (3.10.5) to 5
To use keypad for control, press the Hand/Auto button . Highlight Hand and
press
OK . Highlight Activate and press OK . Speed reference controlled in
the upper selection. Start/stop is controlled via the
/ buttons.
Exercise 2
Key information:
Start/Stop
2 digital inputs are the default settings of the Drive:
Forward = Digital Input 1 by default
Set
Ctrl Signal 1A (3.5.1.1) to DigINSlotA.1
Reverse = Digital Input 2 by default
Set
Ctrl Signal 2A (3.5.1.2) to DigINSlotA.2
NOTE:
These are configured using the Startup Wizard.
Motor Preheat Function
Activated via digital input 4
Set Preheat Function (3.1.2.5) to DIN Control
Set Preheat ON (3.5.1.14) to DIGINSlotA.4