Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Industry, Inc. • 44 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
3.5.7.3 Digital outputs, slot B (Basic)
Table 31: Digital output settings on standard I/O board.
Code Parameter Min Max Unit Default ID Description
P3.5.3.2.1 Basic R01 function 0 35 2 11001
Function selection for Basic
R01:
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = General alarm
6 = Reversed
7 = At speed
8 = Motor regulator active
9 = Preset speed active
10 = Keypad control active
11 = I/O B control activated
12 = Limit supervision 1
13 = Limit supervision 2
14 = Start signal active
15 = Reserved
16 = Fire Mode activation
17 = RTC time chnl 1
control
18 = RTC time chnl 2
control
19 = RTC time chnl 3
control
20 = FB ControlWord B13
21 = FB ControlWord B14
22 = FB ControlWord B15
23 = PID1 in Sleep mode
24 = Reserved
25 = PID1 supervision limits
26 = PID2 supervision limits
27 = Motor 1 control
28 = Motor 2 control
29 = Motor 3 control
30 = Motor 4 control
31 = Reserved (Always
open)
32 = Reserved (Always
open)
33 = Reserved (Always
open)
34 = Maintenance alarm
35 = Maintenance fault
P3.5.3.2.2 Basic R01 ON delay 0.00 320.00 s 0.00 11002 ON delay for relay
P3.5.3.2.3 Basic R01 OFF delay 0.00 320.00 s 0.00 11003 OFF delay for relay
P3.5.3.2.4 Basic R02 function 0 35 3 11004 See P3.5.3.2.1
P3.5.3.2.5 Basic R02 ON delay 0.00 320.00 s 0.00 11005 See P3.5.3.2.2.
P3.5.3.2.6 Basic R02 OFF delay 0.00 320.00 s 0.00 11006 See P3.5.3.2.3.
P3.5.3.2.7 Basic R03 function 0 35 1 11007
See P3.5.3.2.1.
Not visible if only 2 output
relays are installed