Operating Instructions

Operation (Electronic Bypass Only)
Drive Mode
Hand
28
Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391
Building Technologies 2017-09-28
4.
Use the Up and/or Down Arrow buttons to
highlight Activate, and then press OK .
The unit is now operating in the Drive mode using I/O or Fieldbus control. The display
will return to the default display.
Drive Mode – Hand
Hand
mode is used when you want to override the automation system and run the
drive in keypad mode.
You have full control to start/stop the motor, and what the speed reference is from
the keypad directly.
In Hand mode, the Bypass (M1) contactor is opened and the Output (M2) contactor
is closed.
1.
At the drive keypad, press the Hand/Auto button.
2.
Use the Up and/or Down Arrow buttons to
highlight Drive, and then press OK .
3.
Use the Up and/or Down Arrow buttons to
highlight Hand, and then press OK .