Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.10.10
UnitOverTemp Flt
No
Yes
Yes
724
Determines if the automatic reset
feature can reset when a unit over
temperature fault condition
occurs.
P3.10.11
MotorOverTempFlt
No
Yes
Yes
725
Determines if the automatic reset
feature can reset when a motor
over temperature fault condition
occurs.
P3.10.12
External Fault
No
Yes
No
726
Determines if the Automatic Reset
feature can reset when this fault
occurs.
P3.10.13
Underload Flt
No
Yes
No
738
Determines if the Automatic Reset
feature can reset when this fault
occurs.
P3.10.14
Rem Safety Flt
No
Yes
No
728
Determines if the Automatic Reset
feature can reset when this fault
occurs.
P3.10.15
Run Interlock Flt
No
Yes
No
14062
Determines if the Automatic Reset
feature can reset when this fault
occurs.
NOTE:
Automatic reset is allowed for certain faults only. By giving the parameters
Undervoltage flt (P3.10.6) to Wait Time (P3.10.13) the value 0 or 1 you can either
allow or deny the automatic reset after the respective faults.