Operating Instructions
7
Demonstration Configurations
VFD Only
20
Siemens Industry, Inc. 125-1007 Rev.BA
2014-08-14
Demonstration Configurations
VFD Only
The BT300 Demonstration Panel can be used to demonstrate the features and
functions of the stand-alone BT300 Drive. When used in this manner, the Service
Switch (M3) must be turned on for proper operation, and, the Mode Switch must be in
the
VFD position to allow the motor to operate.
The VFD Only configuration uses the following I/O default values (after a factory reset):
I/O Default Value
Description
DI1 Start Forward
DI2 Start Reverse
DI3 External Fault
DI4 Preset Freq 1
DI5 Preset Freq 2
DI6 Fault Reset
AI1 0 to 10 Vdc
AI2 4 to 20 mA
RO1 Run
RO2 Fault
RO3 Ready
AO1 Output Frequency