Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Application Siemens Industry, Inc. • 59
24-hour support +1-800-877-7545 (Dial 2)
3
3.5.14.2 Setpoints
Table 43: PID Setpoints.
Code Parameter Min Max Unit Default ID Description
P3.12.2.1 Keypad setpoint 1 Varies Varies Varies 0 167
P3.12.2.2 Keypad setpoint 2 Varies Varies Varies 0 168
P3.12.2.3 Setpoint ramp time 0.00 300.0 s 0.00 1068
Defines the rising and falling
ramp times for setpoint
changes. (Time to change
from minimum to maximum)
P3.12.2.4
Setpoint source 1
selection
0 16 1 332
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
AI’s and ProcessDataIn are
handled as percent (0.00-
100.00%) and scaled accord-
ing to
Setpoint minimum and maxi-
mum.
NOTE: ProcessDataIn use
two decimals.
P3.12.2.5 Setpoint 1 minimum -200.00 200.00 % 0.00 1069
Minimum value at analog sig-
nal minimum.
P3.12.2.6 Setpoint 1 maximum -200.00 200.00 % 100.00 1070
Maximum value at analog
signal maximum.
P3.12.2.7
Sleep frequency limit
1
0.00 320.00 Hz 0.00 1016
Drive goes to sleep mode
when the output frequency
stays below this limit for a
time greater than that defined
by parameter Sleep delay.
P3.12.2.8 Sleep delay 1 0 3000 s 0 1017
The minimum amount of time
the frequency has to remain
below the Sleep level before
the drive is stopped.
P3.12.2.9 Wake-up level 1 Varies 0.0000 1018
Defines the level for the PID
feedback value wake-up
supervision. Uses selected
process units.
P3.12.2.10 Setpoint 1 boost -2.0 2.0 x 1.0 1071
The setpoint can be boosted
with a digital input.
P3.12.2.11
Setpoint source 2
selection
0 16 2 431 See par. P3.12.2.4