Operating Instructions

Table Of Contents
Siemens Application Siemens Industry, Inc. • 45
24-hour support +1-800-877-7545 (Dial 2)
3
3.5.7.4 Expander slots D and E digital outputs
3.5.7.5 Analog outputs, Slot A (Standard)
Table 32: Slot D/E digital outputs.
Code Parameter Min Max Unit Default ID Description
Application dynamic
output list
Shows only parameters for
existing outputs in slot D/E.
Selections as in Basic R01
Not visible if no digital output
exists in slot D/E.
Table 33: Standard I/O board analog output settings.
Code Parameter Min Max Unit Default ID Description
P3.5.4.1.1 AO1 function 0 19 2 10050
0 = TEST 0% (Not used)
1 = TEST 100%
2 = Output freq (0 -fmax)
3 = Freq reference (0-fmax)
4 = Motor speed (0 - Motor
nominal speed)
5 = Output current (0-I
nMotor
)
6 = Motor torque (0-T
nMotor
)
7 = Motor power (0-P
nMotor
)
8 = Motor voltage (0-U
nMotor
)
9 = DC link voltage (0-1000V)
10 = PID1 output (0-100%)
11 = PID2 output (0-100%)
12 = ProcessDataIn1
13 = ProcessDataIn2
14 = ProcessDataIn3
15 = ProcessDataIn4
16 = ProcessDataIn5
17 = ProcessDataIn6
18 = ProcessDataIn7
19 = ProcessDataIn8
NOTE: For ProcessDataIn,
e.g. value 5000 = 50.00%
P3.5.4.1.2 AO1 filter time 0.00 300.00 s 1.00 10051
Filtering time of analog output
signal. See P3.5.2.2
0 = No filtering
P3.5.4.1.3 AO1 minimum 0 1 0 10052
0 = 0 mA / 0 V
1 = 4 mA / 2 V
Note the difference in analog
output scaling in parameter
P3.5.4.1.4.
P3.5.4.1.4 AO1 minimum scale Varies Varies Varies 0.0 10053
Min scale in process unit
(depends on selection of AO1
function)
P3.5.4.1.5 AO1 maximum scale Varies Varies Varies 0.0 10054
Max scale in process unit
(depends on selection of AO1
function)