Operating Instructions

10
Training Exercises
Exercise Answers/Information
42
Siemens Industry, Inc. 125-1007 Rev.BA
2014-08-14
Prohibited Frequencies
Slow acceleration
View the output speed reactions around the prohibited frequency.
Stopping Types
Ramp vs. Coasting
View the effects
Switching Frequency
Min
Max
Observe the noise differences
Timer Functions
See
3.11 Timer Functions
Program the example.
Exercise Answers/Information
Key information that pertains to the setup of the exercises will be found in this section.
Associated parameters and I/O used will be defined to aid in finding the recommended
solution.
Exercise 1
Key information:
Unit is located in Las Vegas
The Time (2201) setting after factory reset should be set to MST.
Navigate to I/O and then Hardware > Real Time Clock > Time (5.5.2) to verify the
time setting.
Motor nameplate data
Vn = 230 Vac
Set Motor Nom Voltg (3.1.1.1) to 230
In = 0.4A
Set Motor Nom Currnt (3.1.1.4) to 0.4
Fn = 60Hz
Set Motor Nom Freq (3.1.1.2) to 60
Cos phi/PF = 0.7
Set Motor Cos Phi (3.1.1.5) to 0.7
Nn = 1770 rpm
Set Motor Nom Speed (3.1.1.3) to 1770
HP = 1
Set Motor Nom Speed (3.1.1.3) to 1770