Operating Instructions

Demonstration Configurations
7
Electronic Bypass
21
Siemens Industry, Inc. 125-1007 Rev.BA
2014-08-14
Figure 13: VFD Only Default Overlay.
Electronic Bypass
This unit can be used to demonstrate the electronic bypass feature operation. When
used in this manner, the M3 contactor switch must be turned on, and the Mode Switch
must be in the
BYPASS position for proper operation.
The electronic bypass uses the following I/O default values (after bypass wizard use):
Standard I/O
Default Value
Description
DI1 Start Forward
DI2 Remote Safety 1
DI3 Remote Safety 2
DI4 Interlock (Feedback) *
DI5 Overload