Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Application Siemens Industry, Inc. • 63
24-hour support +1-800-877-7545 (Dial 2)
3
3.5.14.6 Pressure Loss Compensation
Table 47: Pressure Loss Compensation.
Code Parameter Min Max Unit Default ID Description
P3.12.6.1 Enable setpoint 1 0 1 0 1189
Enables pressure loss com-
pensation for setpoint 1.
0 = Disabled
1 = Enabled
P3.12.6.2
Setpoint 1 max com-
pensation
Varies Varies Varies Varies 1190
Value added proportionally to
the frequency.
Setpoint compensation =
Max compensation * (Fre-
qOut-MinFreq)/(MaxFreq-
MinFreq)
P3.12.6.3 Enable setpoint 2 0 1 0 1191 See P3.12.6.1.
P3.12.6.4
Setpoint 2 max com-
pensation
Varies Varies Varies Varies 1192 See P3.12.6.2.