Ramp Times
Accel = 6s
– Set Accel Time 1 (3.4.2) to 6
Decel = 3s
– Set Decel Time 1 (3.4.3) to 3
Start/Stop Types
Flying Start
– Set Start Function (3.2.4) to Flying Start
NOTE:
This is configured using the Startup Wizard.
Coast to Stop
– Set Stop Function (3.2.5) to Coasting
NOTE:
This is configured using the Startup Wizard.
Auto Reset
Enable
– Set Automatic Reset (3.10.1) to Enabled
Undervoltage Fault
– Set Undervoltage Flt (3.10.6) to Yes
Wait 2s
– Set Wait Time (3.10.3) to 2
Try 5 times in 80s timeline
– Set Trial Time (3.10.4) to 80
– Set Number of Trials (3.10.5) to 5
To use keypad for control, press the Hand/Auto button . Highlight Hand and
press
OK . Highlight Activate and press OK . Speed reference controlled in
the upper selection. Start/stop is controlled via the
/ buttons.
Exercise 2
Key information:
Start/Stop
2 digital inputs are the default settings of the Drive:
– Forward = Digital Input 1 by default
Set
Ctrl Signal 1A (3.5.1.1) to DigINSlotA.1
– Reverse = Digital Input 2 by default
Set
Ctrl Signal 2A (3.5.1.2) to DigINSlotA.2
NOTE:
These are configured using the Startup Wizard.
Motor Preheat Function
Activated via digital input 4
– Set Preheat Function (3.1.2.5) to DIN Control
– Set Preheat ON (3.5.1.14) to DIGINSlotA.4