Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Industry, Inc. • 86 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
Figure 29. Dead band.
Sleep frequency limit 1 (P3.12.2.7)
Sleep delay 1 (P3.12.2.8)
Wake-up level 1 (P3.12.2.9)
This function will put the drive into sleep mode if the frequency stays below the sleep limit for a longer
period than that set with the Sleep Delay (P3.12.2.8). This means that the start command remains on,
but the run request is turned off. When the actual value goes below or above the wake-up level depend-
ing on the set acting mode, the drive will activate the run request again, if the start command is still on.
Figure 30. Sleep limit, Sleep delay, Wake-up level.
11105.emf
Dead band (P3.12.1.9)
Refer ence
Dead band delay (P3.12.1.10)
Ou t pu t l oc k ed
Act ual val ue
11106.emf
Act ual val ue
Wake- up level
(P3.12.2.9)
Fr equency
Sl eep l i m i t
(P3.12.2.7)
Sleep delay
(P3.12.2.8)
Sl eepRegulating mode Regulating mode