3.5.12 Group 3.10: Automatic reset
Table 40: Autoreset Settings.
Code Parameter Min Max Unit Default ID Description
P3.10.1 Automatic reset 0 1 0 731
0 = Disabled
1 = Enabled
P3.10.2 Restart function 0 1 1 719
The start mode for Automatic
reset is selected with this
parameter:
0 = Flying start
1 = According to par. P3.2.4
P3.10.3 Wait time 0,10 10000,0 s 0,50 717
Wait time before the first
reset is executed.
P3.10.4 Trial time 0,00 10000,0 s 60,00 718
When the trial time has
elapsed, and the fault is still
active, the drive will trip to
fault.
P3.10.5 Number of trials 1 10 4 759
NOTE: Total number of trials
(irrespective of fault type)
P3.10.6
Auto-reset:
Under-voltage
0 1 1 720
Auto-reset permitted?
0 = No
1 = Yes
P3.10.7
Auto-reset:
Over-voltage
0 1 1 721
Auto-reset permitted?
0 = No
1 = Yes
P3.10.8
Auto-reset:
Over-current
0 1 1 722
Auto-reset permitted?
0 = No
1 = Yes
P3.10.9 Auto-reset: AI low 0 1 1 723
Auto-reset permitted?
0 = No
1 = Yes
P3.10.10
Auto-reset: Unit over-
temperature
0 1 1 724
Auto-reset permitted?
0 = No
1 = Yes
P3.10.11
Auto-reset: Motor
overtemperature
0 1 1 725
Auto-reset permitted?
0 = No
1 = Yes
P3.10.12
Auto-reset:
External fault
0 1 0 726
Auto-reset permitted?
0 = No
1 = Yes
P3.10.13
Auto-reset:
Underload fault
0 1 0 738
Auto-reset permitted?
0 = No
1 = Yes