3.5.7.6 Expander slots D to E analog outputs
3.5.8 Group 3.6: Fieldbus Data Mapping
Fieldbus process data out
Values to monitor through fieldbus are:
Table 34: Slot D/E analog outputs.
Code Parameter Min Max Unit Default ID Description
Application dynamic
output list
Shows only parameters for
existing outputs in slot D/E.
Selections as in Basic AO1
Not visible if no analog out-
put exists in slot D/E.
Table 35: Fieldbus data mapping.
Code Parameter Min Max Unit Default ID Description
P3.6.1
Fieldbus data out 1
selection
0 35000 1 852
Data sent to fieldbus can be
chosen with parameter and
monitor value ID numbers.
The data is scaled to
unsigned 16-bit format
according to the format on
keypad. E.g. 25.5 on keypad
equals 255.
P3.6.2
Fieldbus data out 2
selection
0 35000 2 853
Select Process Data Out with
parameter ID.
P3.6.3
Fieldbus data out 3
selection
0 35000 45 854
Select Process Data Out with
parameter ID.
P3.6.4
Fieldbus data out 4
selection
0 35000 4 855
Select Process Data Out with
parameter ID.
P3.6.5
Fieldbus data out 5
selection
0 35000 5 856
Select Process Data Out with
parameter ID.
P3.6.6
Fieldbus data out 6
selection
0 35000 6 857
Select Process Data Out with
parameter ID.
P3.6.7
Fieldbus data out 7
selection
0 35000 7 858
Select Process Data Out with
parameter ID.
P3.6.8
Fieldbus data out 8
selection
0 35000 37 859
Select Process Data Out with
parameter ID.
Table 36. Fieldbus Process Data Out.
Data Value Scale
Process Data Out 1 Output frequency 0.01 Hz
Process Data Out 2 Motor speed 1 rpm
Process Data Out 3 Motor current 0.1 A
Process Data Out 4 Motor torque 0.1 %
Process Data Out 5 Motor power 0.1 %
Process Data Out 6 Motor voltage 0.1 V
Process Data Out 7 DC-link voltage 1 V
Process Data Out 8 Last active fault code