Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Industry, Inc. • 36 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
Auto control place (I/O B): Start, stop and reverse commands are controlled by 2 digital inputs chosen
with parameters P3.5.1.3 and P3.5.1.4. The functionality/logic for these inputs is then selected with pa-
rameter P3.2.7 (in this group).
Hand control place (Keypad): Start and stop commands come from the keypad buttons, while the
direction of rotation is selected by the parameter P3.3.7.
Auto control place (Fieldbus): Start, stop and reverse commands come from fieldbus.
Table 26. Start/Stop Setup menu.
Code Parameter Min Max Unit Default ID Description
P3.2.1 Auto control place 0 1 0 172
Selection of auto control
place (start/stop).
0 = I/O control
1 = Fieldbus control
P3.2.2 Hand/Auto 0 1 0 211
Switch between Hand and
Auto control places
0 = Auto
1 = Hand
P3.2.3 Keypad stop button 0 1 0 114
0 = Stop button always
enabled (Yes)
1 = Limited function of Stop
button (No)
P3.2.4 Start function 0 1 Varies 505
0 = Ramping
1 = Flying start
P3.2.5 Stop function 0 1 0 506
0 = Coasting
1 = Ramping
P3.2.6
I/O A start/stop
logic
0 4 0 300
Logic = 0:
Ctrl sgn 1 = Forward
Ctrl sgn 2 = Backward
Logic = 1:
Ctrl sgn 1 = Forward (edge)
Ctrl sgn 2 = Inverted Stop
Logic = 2:
Ctrl sgn 1 = Forward (edge)
Ctrl sgn 2 = Bckwrd (edge)
Logic = 3:
Ctrl sgn 1 = Start
Ctrl sgn 2 = Reverse
Logic = 4:
Ctrl sgn 1 = Start (edge)
Ctrl sgn 2 = Reverse
P3.2.7
I/O B start/stop
logic
0 4 0 363 See above.
P3.2.8 Fieldbus start logic 0 1 0 889
0 = Rising edge required
1 = State