Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Application Siemens Industry, Inc. • 25
24-hour support +1-800-877-7545 (Dial 2)
3
3.4.2 Basic
See Table 14 in which the basic monitoring values are presented.
NOTE:
Only Standard I/O board status are available in the Monitor menu. Status for all I/O board signals can
be found as raw data in the I/O and Hardware system menu.
Check expander I/O board status when required in the I/O and Hardware system menu.
Table 15: Monitoring menu items.
Code Monitoring value Unit ID Description
V2.2.1 Output frequency Hz 1 Output frequency to motor
V2.2.2 Frequency reference Hz 25 Frequency reference to motor control
V2.2.3 Motor speed rpm 2 Motor speed in rpm
V2.2.4 Motor current A 3
V2.2.5 Motor torque % 4 Calculated shaft torque
V2.2.7 Motor shaft power % 5 Total power consumption of the drive
V2.2.8 Motor shaft power kW/hp 73 Motor shaft power in kW or Hp
V2.2.9 Motor voltage V 6 Voltage fed to the motor.
V2.2.10 DC link voltage V 7 Voltage fed to the motor.
V2.2.11 Unit temperature °C 8 Heat sink temperature
V2.2.12 Motor temperature % 9 Calculated motor temperature
V2.2.13 Analog input 1 % 59 Signal in percent of used range
V2.2.14 Analog input 2 % 60 Signal in percent of used range
V2.2.15 Analog output 1 % 81 Signal in percent of used range
V2.2.16 Motor Preheat 1228
0 = OFF
1 = Heating (feeding DC-current)
V2.2.17 Drive Status Word 43
Bit coded status of drive
B1 = Ready
B2 = Run
B3 = Fault
B6 = RunEnable
B7 = AlarmActive
B10 = DC Current in stop
B11 = DC Brake Active
B12 = RunRequest
B13 = MotorRegulatorActive
V2.2.18 Last active fault 37
The fault code of latest activated fault that has
not been reset.
V2.2.19 Fire mode status 1597
0 = Disabled
1 = Enabled
2 = Activated (Enabled + DI open)
3 = Test mode
V2.2.20 DIN Status Word 1 56
16-bit word where each bit represents the status
of one digital input. 6 digital inputs at every slot
are read. Word 1 starts from input 1 in slot A
(bit0) and goes to input 4 in slot C (bit15).
V2.2.21 DIN Status Word 2 57
16-bit word where each bit represents the status
of one digital input. 6 digital inputs at every slot
are read. Word 2 starts from input 5 in slot C
(bit0) and goes to input 6 in slot E (bit13).