Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Application Siemens Industry, Inc. • 23
24-hour support +1-800-877-7545 (Dial 2)
3
3.3 Application - Quick setup parameter group
The Quick Setup parameter group is a collection of parameters that are most commonly used during in-
stallation and commissioning. They are collected in the first parameter group so that they can be found
fast and easily. However, they can be also reached and edited in their actual parameter groups.
Changing a parameter value in the Quick setup group also changes the value of this parameter in its
actual group.
Table 12. Connection example, Relay board 1.
Relay board 1
Default
Terminal Signal
21 RO1/1 NC
Relay output 1 RUN22 RO1/2 CM
23 RO1/3 NO
24 RO2/1 NC
Relay output 2 FAULT25 RO2/2 CM
26 RO2/3 NO
32 RO3/1 CM
Relay output 3 READY
33 RO3/2 NO
Table 13. Connection example, Relay board 2.
Relay board 2
Default
Terminal Signal
21 RO1/1 NC
Relay output 1 RUN22 RO1/2 CM
23 RO1/3 NO
24 RO2/1 NC
Relay output 2 FAULT25 RO2/2 CM
26 RO2/3 NO
28 TI1+
Thermistor input
29 TI1-
Table 14: Quick setup parameter group.
Code Parameter Min Max Unit Default ID Description
P1.1 Motor nominal voltage Varies Varies V Varies 110
Find this value U
n
on the rat-
ing plate of the motor. See
page 34.
P1.2
Motor nominal fre-
quency
8.00 320.00 Hz 50.00 111
Find this value f
n
on the rat-
ing plate of the motor. See
page 34.
P1.3 Motor nominal speed 24 19200 rpm Varies 112
Find this value n
n
on the rat-
ing plate of the motor.
P1.4 Motor nominal current Varies Varies A Varies 113
Find this value I
n
on the rat-
ing plate of the motor.
P1.5 Motor Cos Phi 0.30 1.00 Varies 120
Find this value on the rating
plate of the motor.
From
Standard I/O board
From term.
#13
From term.
#12
RUN
From
Standard I/O board
From term.
#13
From term.
#6 or 12
RUN