Operating Instructions

Table Of Contents
Siemens Industry, Inc. • 18 Keypad of the drive
24-hour support +1-800-877-7545 (Dial 2)
2.2.5.5 Keypad
2.2.5.6 Fieldbus
Parameters related to different fieldbus boards can also be found in the I/O and Hardware menu. These
parameters are explained in more detail in the respective fieldbus manual.
Table 7: I/O and Hardware menu, Keypad parameters.
Code Parameter Min Max Unit Default ID Description
P5.6.1 Timeout time 0 60 mm 0
Time after which the dis-
play returns to page
defined with parameter
P5.6.2.
0 = Not used
P5.6.2 Default page 0 4 0
0 = None
1 = Enter menu index
2 = Main menu
3 = Control page
4 = Multi-monitor
P5.6.3 Menu index
Set menu index for desired
page and activate with
parameter P5.6.2 = 1.
P5.6.4 Contrast 30 70 % 50
Set contrast of the display
(30...70%).
P5.6.5 Backlight time 0 60 min 5
Set the time until the back-
light of the display turns off
(0...60 min). If set to 0 s,
backlight is always on.
Sub-menu level 1 Sub-menu level 2 Sub-menu level 3
RS-485 Common settings Protocol
Modbus RTU
Modbus parameters
Modbus monitoring
N2
N2 parameters
N2 monitoring
BACNetMSTP
BACNetMSTP parameters
BACNetMSTP monitoring
Ethernet Common settings
Modbus/TCP
Modbus/TCP parameters
Modbus/TCP monitoring
BACnetIP
BACnetIP parameters
BACnetIP monitoring